Level Sensors

ET4 Compact Electrode

Part No. KSE0 ET

for conductive level detection

Electrodes with integrated evaluation electronics for conductive level detection and control

Description
  • Compact construction with integrated evaluation electronics
  • cost-efficient to purchase
  • Easy to install
  • Robust
  • Adjustable sensitivity
  • Adjustable switching delay
  • Potential-free output

The electrodes are used for conductive detection of limit levels. The areas of use cover all sectors where liquid and conductive media are to be detected or controlled.

Limit value measurements (overflow, dry run, max. alarm) as well as min./max. control and pump control (hysteresis) can be implemented.

Construction

The compact electrode ET-4 can be used on site for optimum utilisation of cramped conditions. The electrode consists of an enclosure with up to 5 rod electrodes. The unit can be fastened using a G1¼" connection thread. The enclosure contains the built-in evaluation electronics and is equipped with 1 to 4 output relays depending on the type.

Function

A low alternating current flows once the electrode is submersed into a conductive liquid. This alternating current is evaluated by the switching amplifier (electrode relay). Exceeding an adjustable trigger threshold will energise the according relay.

Sensitivity as well as switching delay and the two-step pump control can be pre-selected directly on the unit using DIP switches.

Typical applications for compact electrodes

  • Shafts/containers with pump control
  • Overflow messages and limit level monitoring
  • Limit level messages for release/counters on stormwater treatment plants
  • Dry run protection
  • and many more
Technical Data
Common
Switching delay

0.5 or 2 seconds

Sensitivity

3 KΩ; 10 KΩ; 30 KΩ; 100 KΩ

Relays
  • 1 to 4 (1 relay per limit value, normally closed)
  • load up to 230 V AC / 3 A (cos. φ 0,9)
  • switching capacity max. 500 VA/150 W
Humidity

90 %, non-condensing

Storage temperature

−20 °C to +85 °C

Operating temperature

−20 °C to +85 °C

Connection thread

G1¼”

Material
  • Enclosure: Polypropylene
  • Protection: IP 65
  • Rods: stainless steel 1.4571
  • Coating: Polyamide

 

max. operating pressure

10 Bar

Rod length

 1 - 3 Meter

Number of electrodes

2 - 5

Power consumption

2 W

Power supply

24 V DC ±15 %

Specifications subject to change.

Downloads
Accessories
Related Products

Haven't found the appropriate product?

Hello
We are glad to have you here! For any question regarding water or digitisation we are happy to answer you call or your email message.
Team NIVUS
Im Täle 2
75031 Eppingen