- Very low in maintenance through non-contact measurement
- Extremely versatile thanks to measurement ranges from 0.07 m to 40 m
- Protection IP 68
- ATEX approval for Ex-Zone 0 and 1
- Alarm output in case of flooding possible
- Resistant to moisture, aggressive environments and heavy temperature fluctuations
The ultrasonic sensors with integrated temperature compensation for connection to NivuMaster- Series evaluation units provide a wide variety of measuring options for liquids.
The sensors provide accurate and reliable readings even in narrow tanks, no matter what measurement range or application. False echoes reflected from built-in obstructive constructions are negligible since they will be avoided automatically.
The sensors are available with 1"-thread or as flange version according to DIN and thus can be installed without any problems.
Typical applications for P-Series sensors
- Level measurements in the water and wastewater sector
- Flow measurements in open flumes and weirs
- Volume measurements in tanks
- Comparative measurements on screens
- Pump control in pump stations
Common | |
---|---|
Process connection | 1"BSP/NPT Standard |
Echo evaluation | Automatic and self-learning echo suppression |
Cable lengths | 5, 10, 20, 30, 50 or 100 m; other lengths upon request |
Ex-Approval | II 2GD Ex m II T6 (II 1GD Ex ia IIC T6 also available, only in connection with intrinsically safe transmitter) |
Protection | IP68 (5 Bar) |
Enclosure material: | Valox 357 PBT PVDF (optional) |
Specifications subject to change.
Optionen | |
---|---|
Flood protection head |
|
Flange type | Flanges DIN DN80 / DN100 / DN150 / DN200, ANSI 3" / 4" / 6" / 8" (only for P-6, P-10 and P-15)
|
Enclosure material: | PVDF for aggressive Medias, max. 70 °C (for P-6, P-10 and P-15) |
Coating of transmitter surface | Sensor face with soft foam coating for dusty bulk solids (only for P-6, P-10 and P-15) |
Specifications subject to change.
P-M3 | |
---|---|
Measurement uncertainty | 1 mm |
Resolution | 0,5 mm |
Beam Angle | <10° |
Operating temperature | −30 to +95 C° (Ex-Zone −30°C do 75°C) |
Transmit frequency | 125 kHz |
Measurement range | 0,07 m - 2,4 m |
Specifications subject to change.
P-3 | |
---|---|
Transmit frequency | 125 kHz |
Measurement uncertainty | +/− 0,25 % of the current measurement range |
Resolution | 2 mm |
Beam Angle | <10° |
Operating temperature | −30 to +95 C° (Ex-Zone −30°C do 75°C) |
Measurement range | 0,125 m - 3 m |
Specifications subject to change.
P-6 | |
---|---|
Transmit frequency | 75 kHz |
Measurement uncertainty | +/− 0,25 % of the current measurement range |
Resolution | 2 mm |
Beam Angle | <10° |
Operating temperature | −40 °C to +90 °C (Ex-Zone −40 °C to +75 °C) |
Measurement range | 0,3 m - 6 m |
Specifications subject to change.
P-S6 | |
---|---|
Resolution | 2 mm |
Measurement uncertainty | +/− 0,25 % of the current measurement range |
Beam angle | < 10° |
Operating temperature | −40 °C to +90 °C (Ex-Zone −40 °C to +75 °C) |
Transmit frequency | 50 kHz |
Measurement range | 0,2 m - 6 m |
Specifications subject to change.
P-10 | |
---|---|
Transmit frequency | 50 kHz |
Measurement uncertainty | +/− 0,25 % of the current measurement range |
Resolution | 2 mm |
Beam Angle | <10° |
Operating temperature | −40 °C to +90 °C (Ex-Zone −40 °C to +75 °C) |
Measurement range | 0,3 m - 10 m |
Specifications subject to change.
P-15 | |
---|---|
Measurement uncertainty | +/− 0,25 % of the current measurement range |
Transmit frequency | 50 kHz |
Resolution | 2 mm |
Beam Angle | < 10° |
Operating temperature | −40 °C to +90 °C (Ex-Zone −40 °C to +75 °C) |
Measurement range | 0,5 m -15 m |
Specifications subject to change.
P-25 | |
---|---|
Measurement uncertainty | +/− 0,25 % of the current measurement range |
Resolution | 2 mm |
Beam Angle | < 10° |
Operating temperature | −40 °C to +90 °C (Ex-Zone −40 °C to +75 °C) |
Transmit frequency | 30 kHz |
Measurement range | 0,6 m - 25 m |
Specifications subject to change.
P-40 | |
---|---|
Measurement uncertainty | +/− 0,25 % of the current measurement range |
Resolution | 2 mm |
Beam Angle | < 7° |
Operating temperature | −40 °C to +90 °C (Ex-Zone −40 °C to +75 °C) |
Transmit frequency | 20 kHz |
Measurement range | 1,2 m - 40 m |
Specifications subject to change.